A
Annex L
Early suppression fast response sprinkler systems
L.1 General
L.1.1 Scope
This
annex
specifies
design
and
installation
requirements
for
Early
Suppression
Fast
Response
(ESFR)
sprinkler
systems.
ESFR
sprinklers
are
quick
acting
high
performance
sprinklers
which
have
the
capability
of extinguishing
fires
within
designated
risks.
There
is
little
room
for
error
in
the
design
and
installation
of
ESFR sprinkler
systems;
the
design
principles
and
the
operating
characteristics
are
significantly
different
from
standard sprinkler
protection.
ESFR
sprinklers
may
not
succeed
with
adverse
design
features
and
non-
compliances,
which may
be
common
practice
when
installing
standard
sprinkler
protection.
It
is
therefore
essential
that
all
the requirements
of
this
annex
are
complied
with,
without
exception,
when
applying
ESFR
protection.
With
the
exception
of
the
clauses
identified
at
1.4.1,
all
the
requirements
of
the
CEA
prevention
specification
4001
are
applicable
when
installing
ESFR
sprinklers.
Preliminary
agreement
of
the
authorities
is
essential
before
selecting
ESFR
sprinklers
to
be
used
in
a
sprinkler
installation.
EFSR
sprinklers
are
mainly
used
if
in-racks
sprinkler
cannot
be
installed
for
technical
reasons.
NOTE:
preliminary
design
considerations
shall
be
carried
out
to
determine
if
the
building
construction
is
suitable
for
the
use
of
ESFR
sprinklers.
L.1.2 Definitions
Sprinkler,
ESFR
pattern
:
Nozzle
with
a
thermo sensitive
sealing
device
which
opens
to
discharge
water, distributing
it
in
a
specified
pattern,
with
sufficient
momentum,
over
a
designated
area
to
achieve suppression
of
a
fire
or
inhibit
growth
when
connected
to
the
appropriate
piping
and
water
supplies.
L.1.3 ESFR sprinklers
ESFR
sprinklers
shall
be
quick
(thermal)
response
and
have
one
of
the
following
temperature
ratings:
Bulbs:
68°C
93°C
Fusible
element:
68
to
74°C
93
to
104°C
The
higher
temperature
ratings
shall
only
be
used
where
needed
because
of
high
ambient
temperature conditions.
The
nominal
k
factor
of
ESFR
sprinklers
shall
be
between
200
and
360.
L.1.4 Application
L.1.4.1
The
following
clauses
of
the
CEA
rules
for
Automatic
Sprinkler
Systems
-
Design
and
Installation
are