170
not
applicable
for
ESFR
sprinkler
protection:
6.1,
6.2,
6.3,
6.4.1,
8.3.2.1,
8.3.2.2,
,
10.2,
10.3,
10.4,
10.5,
11.1.2,
11.2,
11.3,
11.4.1,
11.4.2,
11.4.4,
11.4.5,
11.4.6,
11.4.7,
11.4.9,
11.4.10,
11.4.12,
11.4.13,
11.5,
12.2,
12.4,
12.5,
12.6,
12.8,
12.9.
L.1.4.2 Storage configurations
L1.4.2.1 Flue spaces
Storages
should
have
longitudinal
and
transverse
flues,
which
are:
a)
continuous
for
the
full
height
of
each
block
of
storage;
b)
vertically
aligned;
c)
free
of
stored
goods;
L1.4.2.2
Storage
methods
ST1
ST2
ST3
ST4
ST5
and
ST6
Storages
methods
ST1
-
ST2
ST3
-
ST4
and
ST6
shall
have
flue
spaces
regularly
spaced
and
having
dimensions
as
follows:
(1)
transverse
flues
shall
be
at
least
0,08m
width
and
shall
be
spaced
at
distances
of
not
more
than
3,0m
(see
Figure
L.1);
and
(2)
longitudinal
flues
shall
be
at
least
0,15m
width
and
shall
be
spaced
at
distances
of
not
more
than
3,0m
Figure 29: Storage methods ST2, ST3 and ST4 transverse and longitudinal flues (L1)