EasyManua.ls Logo

CEA 4001 - Annex E Special Requirements for High Rise Systems; Design criteria

Default Icon
190 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
126
Annex E
Special Requirements for High Rise Systems
E.1 Scope
This
Annex
specifies
requirements
particular
to
the
sprinkler
protection
of
multi-storey
buildings
with
a height
difference
between
the
highest
and
lowest
sprinkler
exceeding
45m.
The
requirements
are
applicable to
buildings
intended
for
use
with
occupancies
where
the
hazard
is
classified
as
no
greater
than
Ordinary
Hazard
Group
III.
NOTE:
special
fire
engineering
solutions
are
needed
for
high
rise
systems
with
hazards
greater
than
OH3,
and
specialist
advice
should
be
sought.
E.2 Design criteria
E.2.1 Hazard group
High
rise
sprinkler
systems
shall
comply
with
the
requirements
for
Ordinary
Hazard
Group
III
protection.
E.2.2 Subdivision of high rise sprinkler systems
High
rise
sprinkler
systems
shall
be
sub-divided
into
sprinkler
installations
such
that
the
height
difference between
the
highest
and
lowest
sprinkler
on
any
one
installation
does
not
exceed
45m
(see
Figures
El
and E2).
E.2.3 Zoning
High
Rise
Sprinkler
systems
shall
be
zoned
in
accordance
with
Annex
D.
E.2.4 Standing water pressures at back pressure and alarm valves
The
minimum
standing
pressure
at
any
back
pressure
or
alarm
valve
inlet
shall
be
no
less
than
1,25
times
the static
head
difference
between
the
valve
and
the
highest
sprinkler
on
the
installation.
Back
pressure
valves
controlling
installation
flow
should
operate
correctly
with
a
ratio
of
service
pressure
to
installation
pressure
not
exceeding
1,16:1,
as
measured
by
valve
lift
and
pressure
equalisation
upstream
of
the
back
pressure
valve.
E.2.5 Calculation of distribution pipework for pre-calculated systems
The
main
distribution
pipes,
including
risers
and
drops,
between
the
highest
design
point
in
an
installation and
the
zone
subsidiary
stop
valve
at
the
same
floor
level
shall
be
sized
by
hydraulic
calculations.
The maximum
friction
loss
shall
not
exceed
0,5
bar
at
a
flow
of
1
000
l/min
(see
G.
2.4.2).
Where
sprinkler
protection
is
at
various
floor
levels
in
an
installation
the
allowable
pressure
loss
between
the design
points
and
zone
subsidiary
stop
valves
on
lower
levels,
may
be
increased
by
an
amount
equal
to
the difference
in
static
head
gain
between
the
sprinklers
at
the
level
concerned
and
the
highest
sprinkler
in
the installation.

Table of Contents