8.6.3 Duplicate water supplies
Duplicate
water
supplies
consist
of
two
single
water
supplies
where
each
supply
is
independent
of
the
other. Each
of
the
supplies
forming
part
of
a
duplicate
supply
shall
conform
to
the
pressure
and
flow
characteristics given
in
clause
6.
Any
combination
of
single
supplies
(including
superior
single
supplies)
may
be
used,
with
the
following
limitations:
a)
no
more
than
one
pressure
tank
shall
be
used
for
OH
systems;
b)
no
more
than
one
storage
tank
of
the
reduced
capacity
type
shall
be
used.
Two
or
more
pumps
drawing
water
from
two
independent
suction
tanks
constitute
an
acceptable
duplicate
water
supply.
8.6.4 Combined water supplies
Combined
water
supplies
are
superior
single
or
duplicate
water
supplies
designed
to
supply
more
than
one
fixed
fire
fighting
system,
as
for
example
in
the
case
of
combined
hydrant,
hose
and
sprinkler
installations.
NOTE:
some
countries
may
not
allow
sprinkler
systems
to
be
fed
from
a
combined
supply.
Combined
supplies
shall
fulfil
the
following
conditions:
a)
the
systems
shall
be
fully
calculated;
b)
the
supply
shall
be
capable
of
supplying
the
sum
of
the
simultaneous
maximum
calculated
flows
from
each
system.
The
flows
shall
be
corrected
up
to
the
pressure
required
by
the
most demanding
system;
c)
the
duration
of
the
supply
shall
be
no
less
than
that
required
for
the
most
demanding
system;
d)
duplicate
pipe
connections
shall
be
installed
between
the
water
supplies
and
the
systems.
8.7 Isolation of water supplies
The
connections
between
the
water
sources
and
sprinkler
control
valve
sets
shall
be
arranged
so
as
to
ensure
the
following:
a)
that
servicing
of
main
components
such
as
strainers,
pumpsets,
back
pressure
valves
and
water
meters
is
facilitated;
b)
that
any
problem
occurring
to
one
supply
shall
not
impair
the
operation
of
any
other
source or
supply;
c)
that
maintenance
can
be
carried
out
on
one
supply
without
impairing
the
operation
of
any

Table of Contents