63
If
the
supply
to
the
priming
tank
is
taken
from
the
town
main
forming
a
supply
to
the
sprinkler
installation, the
connection
shall
be
made
upstream
of
the
non-return
valve
on
the
town
main
connection.
The
size
of
the
priming
tank
and
the
pipe
shall
be
in
accordance
with
table16.
T
Table 16: Pump priming tank capacity and pipe size
Hazard
class
Minimum
tank
capacity
Minimum
diameter
of priming
pipe
mm
LH
OH,
HHP
and
HHS
100
500
25
50
9.7
Performance
characteristics
9.7.1
General
The
closed
valve
pressure
shall
not
exceed
12
bars.
The
NPSH
required
by
the
pump
shall
not
exceed
5m
at
flows
up
to
that
defined
in
table
17
Table 17: Pump size
Hazard
Class
Pump
type
Pipework
Pump
nameplate
flow
Pump
inlet
condition
LH-OH
Suction
Pre-calculated
Nominal
as
table
18
Zero
suction
lift
LH-OH
Booster
Pre-calculated
Nominal
as
table
18
Zero
town
main
pressure
HH
Suction
Pre-calculated
1,4x
Flow
required
in
Table
8
Zero
suction
lift
HH
Booster
Pre-calculated
1,4x
Flow
required
in
Table
8
Zero
town
main
pressure
All
hazards
Suction
Fully
Calculated
Q
max
Water
supply
at
low
water level
All
Hazards
Booster
Fully
Calculated
Q
max
Zero
town
main
pressure
Note:
Low
water
level
is
shown
as ”hm”
in
Figure
5
9.7.2
Pre-calculated
systems
-
LH
and
OH
Where
the
pumps
take
water
from
a
storage
tank,
the
characteristic
of
pre-calculated
LH
and
OH
systems shall
conform
to
table
18.