EasyManua.ls Logo

CEA 4001 - Plastic Packaging Recycling Plants

Default Icon
190 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
165
The
sprinklers
shall
have
the
following
characteristics:
-
spray
sprinklers
-
K-factor
min.
57
-
RTI-value
quick
-
upright
Furthermore,
baffles
or
water
shields
for
the
sprinklers
shall
be
installed
to
avoid
cooling
(see
11.3)
and
to protect
them
against
dripping
plastics.
The
hydraulic
design
of
rack
protection
shall
consider
the
following
parameters:
-
area
of
operation
of
90
for
each
level
in
addition
to
the
ceiling
protection
(see
figure)
-
0.5
bar
minimum
pressure
at
sprinkler
K.9.2 Ceiling protection
The
ceiling
protection
shall
have
the
following
characteristics:
-
design:
10
mm/min
over
260
-
K-factor
min.
80
-
RTI-value
special
or
quick
-
protection
area
per
sprinkler
max.
9
K.9.3 Additional measures
Foam
proportioning
with
AFFF
foam
for
rack
and
ceiling
protection
shall
be
provided.
For
limiting
horizontal
fire
spread
vertical
non
combustible
sheet
barriers
shall
be
installed
within
one
double rack
line
and
at
a
maximum
distance
of
every
7
m.
K
K.10 Plastic Packaging Recycling Plants
K.10.1 General
This
concept
is
based
on
fire
tests
and
shows
one
possible
solution
to
provide
an
adequate
protection.
The
different
areas
of
plastic
packaging
recycling
plants
shall
be
protected
by
sprinkler
or
deluge
systems according
to
the
amount
of
combustible
loading
available.
Pneumatic
conveyor
equipment
may
require additional
protection
by
spark
extinguishing
systems.
As
the
fire
extinguishing
of
bulk
and
bale
storage requires
additional
clearing
and
follow-up
extinguishing
measures,
it
is
necessary
to
have
direct
alarm transmission
to
a
permanently
manned
station.
The
protection
concept
should
be
agreed
with
the
authorities
during
the
planning
stage.
K.10.2 Design data of sprinkler systems for recycling plants
A
sprinkler
system
shall
be
used
for:
ƒ
free
pile
storage
ƒ
bale
storage
(compressed
plastic)
ƒ
sorting
area
The
following
equipment
should
be
protected
by
an
additional
water
extinguishing
system
(sprinkler

Table of Contents