65
supply the
flow
rate
equal
to
the
maximum
demand
flow
plus
20%,
at
a
pressure
of
at
least
1
bar,
as
measured
at
the pump
inlet.
This
test
shall
be
carried
out
at
a
time
of
maximum
demand
on
the
main.
9.7.6 Pressure switches
9.7.6.1 Number of pressure switches
Two
pressure
switches
shall
be
provided
to
start
each
pumpset,
connected
in
series
with
normally
closed
contacts.
9.7.6.2 Pump start
The
pumpset
shall
start
automatically
when
the
pressure
in
the
trunk
main
falls
to
a
value
of
not
less
than
0,8
x
P,
where
P
is
the
pressure
when
the
pumps
are
churning.
Where
two
pumpsets
are
installed,
the
second pump
shall
start
before
the
pressure
falls
to
a
value
of
not
less
than
0,6
x
P.
Once
the
pump
has
started,
it shall
continue
to
run
until
stopped
manually.
Where
one
of
the
pumpsets
is
electric
motor
driven
this
shall
be
the
first
to
start.
9.7.6.3 Testing the pressure switches
Means
shall
be
provided
for
testing
each
pressure
switch.
If
any
isolating
valve
is
installed
on
the
connection
between
the
trunk
main
and
any
pump
starting
pressure
switch,
a
back
pressure
valve
shall
be
installed
in parallel
with
the
isolating
valve
so
that
a
fall
in
pressure
on
the
trunk
main
will
be
transmitted
to
the
pressure switch
even
when
the
isolating
valve
is
closed.
9.8 Electrically driven pumpsets
9.8.1 General
9.8.1.1
In
some
countries
the
authorities
allow
two
electrically
driven
pumps
under
certain
conditions.
9.8.1.2
The
electric
supply
system
shall
be
available
at
all
times.
9.8.1.3
Documentation,
such
as
installation
drawings,
main
supply and
transformer
diagrams
and connections
for
supplying
the
pump
controller
panel
as
well
as
motor,
control
alarm
circuits
and
signals
shall
be
kept
available
in
the
sprinkler
valve
or
pump
room
and
be
up
to
date
at
all
times.
9.8.1.4
The
pump
shall
be
fully
operational
within
15
seconds
of
the
beginning
of
any
starting
sequence.
9.8.2 Electricity supply
9.8.2.1
The
supply
to
the
pump
controller
shall
be
solely
for
the
use
of
the
sprinkler
pumpset
and
separate
from
all
other
connections.
Where
permitted,
the
electrical
supply
to
the
pump
controller
shall
be
taken
from
the
input
side
of
the
main
switch
on
the
incoming
supply
to
the
premises
and
where
this
is
not
permitted,
by
a
connection
from
the
main
switch.
The
fuses
in
the
pump
controller
shall
be
of
high
rupturing
capacity,
capable
of
carrying
the
stalled
motor current
for
a
period
of
not
less
than
75
%
of
the
time
needed
for
the
motor
windings
to
fail
and
thereafter
be able
to
carry
the
normal
current
plus
100%
for
a
minimum
of
5
hours.
9.8.2.2
All
cable
shall
be
protected
against
fire
and
mechanical
damage.
The
protection
shall
be
accepted
by
the
authorities.
NOTE
1:
all
wiring
associated
with
the
electric
motor
driven
pump,
including
the
monitoring
circuits,

Table of Contents