66
should
be
in
accordance
with
the
appropriate
regulations
for
electrical
installations.
To
protect
cables
from
direct
exposure
to
fire
they
should
be
run
outside
the
building
or
through
those
parts
of
the
building
where
the
fire
risk
is
negligible
and
which
are
separated
from
any
significant
fire risk
by
walls,
partitions
or
floors
with
a
fire
resistance
of
not
less
than
60
min,
or
they
should
be given
additional
direct
protection.
NOTE
2:
it
is
strongly
recommended
that
the
cable
be
buried.
9.8.3 Switchboard
9.8.3.1
The
switchboard
for
the
premises
shall
be
situated
in
a
fire
compartment
used
for
no
other
purpose
than
for
electrical
power
supplies,
any
other
location
shall
be
approved
by
the
authorities.
The
electrical
connections
in
the
main
switchboard
shall
be
such
that
the
supply
to
the
pump
controller
is
not
isolated
when
isolating
other
services.
9.8.3.2
Each
switch
on
the
dedicated
power
feed
to
the
sprinkler
pump
shall
be
labelled:
SPRINKLER
PUMP
MOTOR
SUPPLY
-
NOT
TO
BE
SWITCHED
OFF
IN
THE
EVENT
OF
FIRE
The
letters
on
the notice
shall
be
at
least
10mm
high
and
white
on
a
red
background.
9.8.4 Installation between the main switchboard and the pump controller
9.8.4.1
The
current
for
calculating
the
correct
dimension
for
the
cable
shall
be
determined
by
taking
the largest
possible
full
load
current
and
adding
50%.
The
cable
shall
furthermore
be
able
to
carry
the
largest possible
starting
current
for
10
seconds.
9.8.5 Pump controller
9.8.5.1
The
pump
controller
shall
be
able:
a)
to
start
the
motor
automatically
on
receiving
a
signal
from
the
pressure
switches;
b)
to
start
the
motor
manually;
c)
to
stop
the
motor
by
manual
operation
only.
The
controller
shall
be
equipped
with
an
ammeter.
9.8.5.2
Except
in
the
case
of
submersible
pumps,
the
pump
controller
shall
be
situated
in
the
same
room
(pump
room)
as
the
electric
motor
and
pump.
In
the
case
of
submersible
pumps
a
duplicate
plate
with
its
characteristics
shall
be
affixed
to
the
pump
controller.
9.8.5.3
Contacts
shall
comply
with
utilisation
category
AC-3
of
IEC
947.
9.8.6 Monitoring of pump operation
9.8.6.1
The
following
conditions
shall
be
monitored:
-
power
available
to
the
motor
on
all
three
phases;
-
pump
on
demand;
-
pump
running.
9.8.6.2
All
monitored
conditions
shall
be
visually
indicated
individually
in
the
pump
room.
They
should
also