157
Annex K
Protection of Special Hazards
National
requirements
shall
be
taken
into
consideration.
The
following
product
examples
need
special
consideration.
K.1 Aerosols
Protection
for
aerosol
storages
shall
be
in
accordance
with
table
K
1.
Precautions
shall
be
taken
to
avoid
projection
of
aerosol
containers.
The
maximum
area
of
aerosol
storage
and
any
containment
shall
be
considered
and
the
authorities
shall
be consulted.
Table 52: Protection criteria for aerosol storage (K1)
Maximum
storage
height
m
Sprinkler
K
factor
Minimum
density
mm/min
Area of
operation
Aerosol
contents
alcohol based
hydrocarbon
based
STI
-
Free
standing
storage
1,5
-
115
160
12,5
260
-
1,5
115
160
25,0
300
ST4
Palletized
rack
storage
Maximum
vertical
height
between
sprinkler
rows
m
12,5
plus
in-
rack
sprinklers
260
1,8
-
115/160
(1)
80/115
(2)
12,5
(3)
260
-
1,8
115/160(1)
80/115(2)
25,0
(3)
300
NOTE:
1
ceiling
sprinkler
protection.
NOTE:
2
intermediate
level
sprinkler
protection.
NOTE:
3
intermediate
level
sprinkler
protection
shall
be
installed
in
accordance
with
Category
III
or
IV
layout
but
at
the
maximum
vertical
height
separations
between
sprinkler
rows
given
in columns
2
and
3.