19
Thermal
response.
The
authorities
shall
evaluate
the
results
in
function
of
the
demand
characteristics
of
the
installation
and,
if
necessary,
the
sprinklers
shall
be
changed.
1.4.4 Responsible person
The
owners
shall
appoint
a
responsible
person
and
a
substitute,
who
after
they
have
been
given
the
necessary instructions
by
the
installer,
shall
ensure
that
the
system
remains
in
working
condition.
The
name,
address and
telephone
number
of
the
person
responsible
for
the
installation,
as
well
as
those
of
his
or
her
substitute, shall
be
prominently
displayed
in
the
sprinkler
valve
room.
The
owner
shall
ensure
that:
-
the
installation
conforms
to
the
rules
at
all
times;
-
the
installation
is
in
working
order
at
all
times;
-
the
installation
is
checked,
maintained
and
tested
in
accordance
with
the
installers'
instructions
and
the
CEA
rules;
-
the
installation
is
inspected,
by
contract,
at
least
once
a
year
by
one
of
the
authorities'
inspectors
appointed
by
the
insurers;
-
any
faults
or
deficiencies
are
corrected
within
the
time
limits
laid
down
by
the
authorities.
2
2 Definitions
For
the
purposes
of
these
rules,
the
following
definitions
apply.
'A'
gauge
A
pressure
gauge
connected
to
a
town
main
connection,
between
the
supply
pipe
stop
valve
and
the
check
valve.
accelerator
A
device
that
reduces
the
delay
in
operation
of
a
dry
alarm
valve,
or
composite
alarm
valve
in
dry
mode,
by
early
detection
of
the
drop
in
air
or
inert
gas
pressure
on
sprinkler
operation.
alarm
test
valve
A
valve
through
which
water
may
be
drawn
to
test
the
operation
of
the
water
motor
fire
alarm
and/or
of
any
associated
electric
fire
alarm.
alarm
valve
A
check
valve,
of
the
wet,
dry
or
composite
type
that
also
initiates
the
water
motor
fire
alarm
when
the
sprinkler
installation
operates.
alarm
valve,
alternate
An
alarm
valve
suitable
for
a
wet,
dry
or
alternate
installation.
alarm
valve,
dry
An
alarm
valve
suitable
for
a
dry
installation;
and/or
in
association
with
a
wet
alarm
valve
for
an
alternate

Table of Contents