18
The
sprinkler
system
shall
be
periodically
inspected
at
least
once
a
year
by
the
authorities’
inspector.
The
inspection
report
shall
confirm
that
the
system
is
in
accordance
with
the
rules,
well
maintained
and
in full
working
order.
Any
faults
and
deficiencies
shall
be
noted
in
the
inspection
report
and
the
authorities shall
specify
the
time
limits
for
rectification.
1.4.3.2 Long-term Reliability Inspection
The
pipes
and
the
sprinkler’s
heads
shall
be
inspected
in
great
detail
at
least
every
25
years
for
wet
installations
and
15
years
for
dry
or
alternate
installations.
1.4.3.2.1. Pipes
The
pipework
shall
be
internally
and
externally
inspected.
At
least
one
range
pipe
shall
be
inspected
per
100
sprinklers
over
an
appropriate
length.
Not
less
than
two-range
pipe
lengths
per
control
valve
set
shall
be
examined.
Other
pipes
shall
be
inspected
if
the
range
pipe
examined
exhibits
an
unacceptable
level
of
corrosion
or
tuberculation.
The
pipework
shall
be
hydrostatically
tested
to
a
pressure
equal
to
the
maximum
static
pressure
or
12
bar, whichever
is
the
higher
pressure
for
a
period
of
2
hours
and,
where
possible,
the
pipe
work
shall
be thoroughly
flushed
out.
All
defects
which
can
adversely
affect
the
hydraulic
performance
of
the
system
shall
be
eliminated.
The
national
authorities
shall
evaluate
the
pipe
defects.
1.4.3.2.2 Sprinklers
A
number
of
sprinklers
shall
be
removed
and
inspected.
Table
1
specifies
the
scope
of
sampling
as
a
function
of
the
total
number
of
sprinklers
installed
in
the
premises.
T
Table 1 :Minimum number of sprinklers per type to be inspected
Total
number
of
sprinklers
installed
(n)
Minimum
number
of
sprinklers
to
be inspected
(batch)
n
<
5000
20
5000
<
n
<
10000
40
10000
<
n
<
20000
60
20000
<
n
<
30000
80
n
>
30000
100
Sprinklers
removed
for
inspection
shall
be
visually
inspected:
The
following
tests
shall
be
carried
out
on
samples
selected
from
the
batch
of
sprinklers:
Operating
temperature;
Function
and
minimum
operating
pressure;
Leak
resistance;
K
factor;
And
where
appropriate: