168
Upon
triggering
of
the
deluge
system,
the
conveyor
and
screening
equipment
of
the
appropriate
area
shall
be
disabled
automatically.
The
water
demand
for
the
local
protection
equipment
in
the
operating
areas
shall
be
hydraulically
taken
into account.
K.10.4 Monitoring of sprinkler or deluge system
The
sprinkler
resp.
deluge
systems
shall
be
monitored
for
operational
availability.
K.10.6 Spark extinguishing systems in recycling plants
A
spark
extinguishing
system
(CEA
4033)
shall
be
used
for
pneumatic
conveyor
equipment
for
waste
material
and
dust
(e.g.
baling
presses,
filter
systems,
air
separators,
press
waste
container
station).