103
out under
contract
by
the
system
installer
or
a
similarly
qualified
company.
After
an
inspection,
check,
test
service
or
maintenance
procedure
the
system,
and
any
automatic
pumps, pressure
tanks
and
gravity
tanks
shall
be
returned
to
the
proper
operational
condition.
NOTE
:
if
appropriate,
the
user
should
notify
interested
parties
of
the
intent
to
carry
out
tests
and/or
of the
results.
18.1.2 Replacement sprinklers
A
stock
of
spare
sprinklers
shall
be
kept
on
the
premises
as
replacements
for
operated
or
damaged
sprinklers. Spare
sprinklers,
together
with
sprinkler
spanners
as
supplied
by
the
manufacturer,
shall
be
housed
in
a cabinet
or
cabinets
located
in
a
prominent
and
easily
accessible
position
where
ambient
temperature
does
not exceed
38°C.
The
number
of
the
spare
sprinklers
shall
be
not
less
than:
a)
6
for
LH
installations;
b)
24
for
OH
installations;
c)
36
for
HHP
and
HHS
installations.
The
stock
shall
be
replenished
promptly
after
spares
are
used.
Where
installations
contain
high-temperature
sprinklers,
sidewall
or
other
variations
of
sprinkler
pattern
or contain
multiple
controls,
an
adequate
number
o
these
spares
shall
also
be
maintained.
18.1.3 Precautions and procedures when a system is not fully operational
18.1.3.1 Minimising the effects
Maintenance,
alterations
and
repair
of
systems
which
are
note
fully
operational
shall
be
carried
out
such
as
to minimize
the
time
and
extent
of
non-operation.
When
an
installation
is
rendered
inoperative
the
user
shall
implement
the
following
measures:
a)
the
fire
authorities
shall
be
informed
if
the
alarm
is
connected
to
the
fire
brigade;
b)
alterations
and
repairs
to
an
installation
or
its
water
supply
(except
possibly
a
life
safety installation
(see
Annex
F)
shall
be
carried
out
during
normal
working
hours;
c)
any
hot
work
shall
be
subject
to
a
permit
system.
Smoking
and
naked
lights
shall
be
prohibited
in affected
areas
during
the
progress
of
the
work;
d)
when
an
installation
remains
inoperative
outside
working
hours
all
fire
doors
and
fire
shutters
shall remain
closed;
e)
fire
extinguishing
appliances
shall
be
kept
readiness,
with
trained
personnel
available
to
handle them;
f)
as
much
as
possible
of
the
installation
shall
be
retained
in
an
operative
condition
by
blanking