131
When
a
zone
(or
zones)
is
charged
or
recharged
with
water
after
draining,
the
flushing
valve(s)
(see
D.3.3)
shall
be
used
to
check
that
water
is
available
in
the
zone
(or
zones).
Individual
alarm
valves
in
a
duplicate
control
valve
set,
where
required,
shall
be
separately
serviced, provided
the
water
supply
to
the
installation
is
maintained.
The
following
procedure
shall
be
followed
before
servicing
duplicate
control
valve
sets:
-
the
stop
valves
to
the
duplicate
alarm
valve
shall
be
checked
and
if
necessary
opened.
One
of the
stop
valves
to
the
alarm
valve
to
be
serviced
shall
be
closed
and
an
alarm
test
(see
18.3.2.3) carried
out
immediately
on
the
other
alarm
valve;
-
if
water
is
not
available,
the
stop
valve
shall
be
opened
immediately,
and
the
fault
rectified before
proceeding.

Table of Contents