82
11.5.1 General
Sprinklers
protecting
double
row
racks
shall
be
positioned
in
the
longitudinal
flue
spaces,
preferably
in
the intersection
with
the
transverse
flue
(see
Figures
9
and
10).
Whenever
any
rack
or
structural
steelwork
is
likely
to
interfere
significantly
with
the
water
discharge
from the
sprinklers,
additional
sprinklers
shall
be
provided
and
taken
into
account
in
the
flow
calculation.
It
shall
be
ensured
that
water
from
sprinklers
operating
at
intermediate
levels
can
penetrate
the
goods
stored. The
distance
between
goods
stored
in
racking
and
placed
back
to
back
shall
be
at
least
0,15m,
and
if necessary
pallet
stops
should
be
fitted.
There
shall
be
a
clearance
of
at
least
0,15m
from
the
sprinkler deflectors
to
the
top
of
the
storage.