108
The
electrolyte
level
and
density
of
all
open
nickel-cadmium
cells
(including
those
in
diesel
engine
starter batteries
and
those
for
control
panel
power
supplies)
shall
be
checked.
If
the
density
is
low
the
battery
charger shall
be
checked
and
if
necessary
repaired
or
replace.
If
the
charger
is
working
normally,
the
battery
or batteries
affected
shall
be
replaced.
Any
secondary
electrical
supplies
from
diesel
generators
shall
be
checked
for
satisfactory
operation.
18.4.2.7 Stop valves
All
stop
valves
controlling
the
flow
of
water
to
sprinklers
shall
be
operated
to
ensure
that
they
are
in
working order,
and
securely
refastened
in
the
correct
mode.
This
shall
include
the
stop
valves
on
all
water
supplies,
at
the
alarm
valve(s)
and
all
zone
or
other
subsidiary
stop
valves.
18.4.2.8 Flow switches
Flow
switches
shall
be
checked
for
correct
function.
18.4.2.9 Replacement parts
Replacement
parts
held
as
spare
shall
be
checked
for
number
and
condition.
18.4.3 Half-yearly routine
18.4.3.1 General
The
following
checks
and
inspections
shall
be
made
at
intervals
of
not
more
than
6
months.
18.4.3.2 Dry alarm valves
Dry
alarm
valves,
and
any
accelerators
and
exhausters,
in
dry
pipe
installations
and
subsidiary
extensions shall
be
exercised
in
one
of
the
following
ways,
as
appropriate:
a)
the
inspection
cover
plate
shall
be
removed
and
the
moving
parts
shall
be
operated
manually;
b)
if
a
screw-down
diaphragm
interlocking
key
type
subsidiary
stop
valve
is
fitted
downstream
of
the alarm
valve,
subsidiary
stop
valve
shall
be
closed,
the
space
between
the
dry
pipe
valve
clack
and the
underside
of
the
subsidiary
valve
shall
be
primed
with
water,
and
the
installation
drain
valve shall
be
opened.
NOTE
:
alternate
installations
need
not
be
tested
in
this
way
since
they
are
exercised
twice
a
year
as
a result
of
the
change-over
from
wet
to
dry
operation
and
back.
18.4.3.3 Fire brigade and remote central station alarm
The
electrical
installation
shall
be
checked.
18.4.4 Yearly routine
18.4.4.1 General
The
following
checks
and
inspection
shall
be
made
at
intervals
of
not
more
than
12
months.