EasyManua.ls Logo

CEA 4001 - Page 124

Default Icon
190 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
124
distribution
pipe spur,
as
appropriate.
The
valve
outlet
shall
be
fitted
with
a
brass
plug
cap.
D.3.4 Monitoring
Zoned
sprinkler
installations
shall
be
provided
with
tamperproof
devices
to
monitor
the
status
of:
a)
each
stop
valve
(i.e.
either
fully
open
or
not
fully
open),
including
subsidiary
stop
valves,
capable
of
interrupting
the
flow
of
water
to
sprinklers;
b)
water
flow
into
each
zone
immediately
downstream
of
each
zone
subsidiary
stop
valve,
to indicate
the
operation
of
each
zone,
by
means
of
a
water
flow
alarm
switch
capable
of
detecting
a
flow
equal
to
or
greater
than
that
from
any
single
sprinkler;
c)
water
flow
through
each
main
installation
control
valve
set.
D.3.5 Zone test and drainage facilities
Permanent
test
and
drainage
facilities
shall
be
provided
immediately
downstream
of
the
water
flow
alarm switch
on
each
zone.
The
test
facility
shall
simulate
operation
of
any
single
sprinkler
head.
Adequate provision
shall
be
made
for
the
disposal
of
waste
water.
D.3.6 Installation control valve set
The
main
control
valve
set
of
a
zoned
sprinkler
installation
shall
have
tow
stop
valves,
one
on
each
side
of
a single
alarm
valve
with
a
bypass
connection
of
the
same
nominal
bore
around
all
three
valves,
fitted
with
a normally
closed
stop
valve
(see
Figure
D1).
Each
of
the
three
stop
valves
shall
be
fitted
with
tamper
proof devices
to
monitor
their
status
(i.e.
fully
open
or
not
fully
open).
D.3.7 Installation monitoring and alarms
The
monitoring
devices
required
by
D.3.4
and
D.3.6
shall
be
electrically
connected
to
a
control
and indicating
panel,
located
on
the
premises,
where
the
following
indications
and
warnings
shall
be
given:
a)
by
means
of
green
visual
indicators
that
each
monitored
stop
valve
is
in
its
correct
operational position;
b)
by
means
of
audible
devices
and
amber
visual
indicators
that
one
or
more
control
valve
sets
are not
fully
open;
c)
by
means
of
audible
devices
and
amber
visual
indicators
that
one
or
more
zone
subsidiary
stop valves
are
not
fully
open;
d)
by
means
of
audible
devices
and
amber
visual
indicators
that
the
static
pressure
in
any
trunk main
supplying
the
system
has
fallen
to
a
value
0,5bar
or
more
below
the
normal
static
pressure;
e)
by
means
of
audible
devices
and
red
visual
indicators
that
water
is
flowing
into
the
installation;
f)
by
means
of
audible
devices
and
red
visual
indicators
that
water
is
flowing
into
one
or
more zones.

Table of Contents