135
G.2.1.4
Risers
or
drops,
connecting
distribution
pipes
to
ranges,
and
pipes
connecting
single
sprinklers, other
than
arm
pipes,
shall
be
considered
as
distribution
pipes
and
sized
accordingly.
G.2.2 Location of Design Points
G.2.2.1
The
design
point
shall
be
located
at
the
point
of
connection
of
a
horizontal
distribution
pipe
to
one
of
the
following:
-
a
range
pipe;
-
a
riser
or
drop
connecting
ranges
to
distribution
pipes;
-
a
pipe
feeding
a
single
sprinkler.
The
maximum
number
of
sprinklers
downstream
of
each
design
point
is
specified
in
Tables
G4
and
G5.
The design
point
is
located
by
counting
from
the
hydraulically
most
remote
sprinkler
in
the
array.
G.2.2.2
In
Light
Hazard
installations
the
design
point
shall
be
located
downstream
of
the
sprinkler
identified
in
Table
G4
column
3.
G.2.2.3
In
Ordinary
and
High
Hazard
installations
the
design
point
shall
be
located
downstream
of
the junction
of
distribution
pipes
and
range
pipes
in
accordance
with
Table
G5
column
3.
Where
the
number
of
sprinklers
on
one
array
in
a
room,
or
on
a
single
distribution
pipe,
is
less
than
or
equal
to
the
number
of
sprinklers
for
which
the
distribution
pipes
are
designed,
indicated
in
Table
G5
column
2,
the
design
point
shall
be
positioned
downstream
of
the
point
of
connection
to
the
distribution
pipe
of
the range
or
the
array
hydraulically
nearest
to
the
control
valve
set.
Table 40: Location of design points – LH (G4)
Hazard
class
Number
of
sprinklers
on
a
range,
in
a
room
Location
of
design
point
downstream
of
n
th
sprinkle
r
where
n
is
LH
≤3
≥4
3
4
Table 41: Location of design points - OH, HHP and HHS (G5)
Hazard
class
Number
of
sprinklers on
a
distribution
pipe, in
a
room
Location
of
design
point
on
a
distributio
n
pipe
junction
to
a
range
holding
n
th
sprinkler
where
n
is
Range
layout
OH
>
16
17
two
end-side
HHP
and
HHS
>
18
>
48
19
49
all
except
two
end-side
all
NOTE
1:
figure
H2
illustrates
typical
range
pipe
arrays.
NOTE
2:
examples
of
pie
layouts
with
the
appropriate
design
points
are
given
in
Figure
H3
for
LH, Figure
H4
for
OH
and
Figures
H5,
H6
and
H7
for
HHP
and
HHS.