175
L
L.2.3 Spacing and location of sprinklers
L.2.3.1
The
area
of
coverage
of
ESFR
sprinklers
shall
be
not
less
than
7,5m
2
and
not
more
than
9m
2
.
The distance
between
sprinklers
shall
be
in
accordance
with
table
L3.
Table 63: Distance between sprinklers (L3)
Maximum
height
ceiling
m
Distance
between
sprinklers
in
m
min
max
9,1
2,4
3,7
12,2
2,4
3
L.2.3.2
The
centre
line
of
the
sprinkler
heat-sensitive
element
shall
be
between
0,1
to
0,33m
below
the
roof
or
ceiling
for
an
ESFR
sprinkler
with
a
K
factor
of
200.
The
centre
line
of
the
sprinkler
heat-sensitive
element
shall
be
between
0,1
to
0,45m
below
the
roof
or
ceiling
for
an
ESFR
sprinkler
with
a
K
factor
of
360.
Where
the
roofs
or
ceilings
are
constructed
using
beams
and
girders
or
profiled
paneling,
sprinklers
should
be located
in
bays
rather
than
under
beams.
Bays
formed
by
this
method
of
construction
should
not
exceed
0,75m depth.
Where
the
ceiling
is
profiled,
the
distance
from
the
ceiling
to
the
sprinkler
shall
be
measured
from
the
top
of
the
profile,
see
figure
L2
to
L6.
Where
this
is
not
practical,
the
roof
or
ceiling
shall
be
underdrawn
by
a
suspended
ceiling.
Figures
L2,
L3,
L4,
L5,
L6:
Sprinkler
location
relative
to
obstacles
Figure 30:L2