31
3)
the
net
positive
suction
head
(NPSH)
graph;
4)
a
statement
of
the
power
output
of
each
prime
mover;
c)
the
installer's
data
sheet
showing
the
pump
set
installed
performance
pressure/flow
characteristics,
at
the
control
valve
'C'
gauge
for
normal
water
level
and
for
low
water
level
'X'
(see
Figures
4
and
5),
and
at
the
pump
outlet
pressure
gauge
for
normal
water
level;
d)
the
height
difference
between
the
control
valve
'C'
gauge
and
the
pump
delivery
pressure
gauge;
e)
the
installation
number
and
the
hazard
classification(s);
f)
the
available
and
the
specified
NPSH
at
maximum
required
flow;
g)
the
minimum
depth
of
water
cover
in
the
case
of
submersible
pumps;
In
addition
where
the
pipework
is
fully
calculated
the
following
details
shall
be
provided;
h)
the
demand
pressure/flow
characteristic
for
the
hydraulically
most
unfavourable
and
most
favour-
able
area
of
operation
calculated
at
the
control
valve
'C'
gauge.
3.4.4.5 Pressure tank
The
following
details
shall
be
provided:
a)
the
location;
b)
the
total
volume;
c)
the
volume
of
stored
water;
d)
the
air
pressure;
e)
the
height
of
the
highest
sprinkler
above
the
bottom
of
the
tank;
f)
details
of
the
means
of
replenishment.
3.4.4.6 Water storage tank
The
following
details
shall
be
provided:
a)
the
location;
b)
the
total
volume;
c)
the
volume
and
duration
of
stored
water;
d)
inflow
for
reduced
capacity
tanks;
e)
vertical
distance
between
the
pump
centre
line
and
the
tank
low
water
level
'X';
f)
structural
details
of
the
tank
and
roof;