49
Table 11
:
: Minimum water volume for precalculated HHP and HHS systems
Design
density
not
exceeding
mm/min
Minimum
water
volume
m
3
Wet
systems
Dry
systems
7,5
10,0
12,5
15,0
17,5
20,0
22,5
25,0
27,5
30,0
225
275
350
425
450
575
650
725
800
875
280
345
440
530
560
720
815
905
1
000
1
090
8.3.2.2 Calculated systems
The
minimum
water
volume
shall
be
calculated
by
multiplying
the
maximum
demand
flow
by
the
following
operating
times:
-
LH
30
minutes
-
OH
60
minutes
-
HH
90
minutes
8.3.3 Refill rates for full capacity tanks
The
water
source
shall
be
capable
of
refilling
the
tank
in
no
more
than
36
hours.
The
outlet
of
any
feed
pipe
shall
be
situated
at
least
2,0m
away
from
the
pump
inlet,
measured
horizontally.
8.3.4 Reduced capacity tanks
The
following
conditions
shall
be
met
for
reduced
capacity
tanks:
a)
the
inflow
shall
be
from
a
town
main
and
shall
be
automatic,
via
at
least
two
mechanical
float
valves;
b)
the
effective
capacity
of
the
tank
shall
be
no
less
than
that
shown
in
Tables
12;
c)
the
tank
capacity
plus
the
inflow
shall
be
sufficient
to
supply
the
system
at
full
capacity
as
specified
in
8.3.2;
d)
it
shall
be
possible
to
check
capacity
of
the
inflow;
e)
the
inflow
arrangement
shall
be
accessible
for
inspection.