Table 22: Maximum coverage and spacing for sidewall sprinklers
Hazard class
Maximum
area per
sprinkler
Spacing along walls
Room width
(w)
m
Room length
(l)
m
Rows of side
wall sprinklers
Spacing pattern
(horizontal plane)
between
sprinkle
rs
m
sprinkler to
end of wa
ll
m
LH
17,
0
4,6
2,3
w ≤ 3,7
any
1
single line
3,7 < w ≤ 7,4
≤ 9,2
2
standard
>9,2
2
staggered
w >7,4
any
2
(1)
standard
OH
9,0
3,4
(2)
1,8
w ≤ 3,7
any
1
single line
3,7 < w ≤ 7,4
≤6,8
2
standard
>6,8
2
staggered
w>7,4
any
2
(1)
standard
NOTE
1:
an
additional
row
o
rows
of
roof
or
ceiling
sprinklers
is
needed.
NOTE
2:
may
be
increased
to
3,7m
provided
the
ceiling
has
a
fire
resistance
of
not
less
than
120
minutes.
NOTE
3:
the
sprinkler
deflectors
shall
be
located
between
0,1m
and
0,15m
below
the
ceiling
and
between
0,05m and
0,15m
horizontally
from
the
wall.
NOTE
4: there
shall
be
no
obstruction
at
the
ceiling
within
a
square
extending
along
the
wall
1,0m
on
each
side
of
the
sprinkler
and
1,8m
perpendicular
to
the
wall.
NOTE
5:
where
beams
or
girders
occur,
the
bays
thus
formed
shall
be
protected
separately.
NOTE
6:
see
also
clause
12.2.5.1.
Figure 6 - Ceiling sprinkler spacing
 6