84
the
next highest
row
(see
Figure
9).
The
horizontal
distance
between
sprinklers
shall
not
exceed
3,75m
and
the product
of
the
horizontal
distance
and
the
vertical
distance
between
sprinklers
shall
not
exceed
9,8m².
In
the
case
of
Category
III
or
IV
goods,
sprinklers
shall
be
installed
in
the
longitudinal
flue
at
the
intersection with
each
transverse
flue
(see
Figure
10).
The
horizontal
distance
between
sprinklers
shall
not
exceed
1,9m and
the
product
of
the
horizontal
distance
and
the
vertical
distance
between
sprinklers
shall
not
exceed
4,9m².
11.5.4 Numbers of rows of sprinklers at each level
The
number
of
sprinkler
rows
per
level
shall
be
determined
by
the
total
width.
When
racking
is
placed
back
to
back
the
total
width
shall
be
calculated
by
adding
together
the
width
of
each
rack
and
the
distance
between them.
1
row
of
sprinklers
per
level
shall
be
installed
for
every
3,2m
of
rack
width.
They
shall
be
installed
in
the flue
spaces
wherever
possible.
11.5.5 HHS intermediate sprinklers in non-shelved racks
Intermediate
sprinklers
shall
be
provided
for
palletised
rack
storage
and
multiple
row
drive
through
storage
(see
type
ST4
in
Table
5):
a)
single
row
racks
not
more
than
3,2m
wide
shall
be
protected
by
single
rows
of
sprinklers
fitted
on the
side
of
the
stack
not
used
for
access
at
the
tier
levels
shown
in
Figures
9
and
10;
b)
double
row
racks
not
more
than
3,2m
wide
shall
be
protected
by
sprinklers
centrally
in
the longitudinal
flue
space,
at
the
stack
ends,
and
at
the
tier
levels
shown
in
Figures
9
and
10;
c)
double
or
multiple
row
racks
more
than
3,2m
wide,
but
not
more
than
6,4m
wide
shall
be protected
by
two
rows
of
sprinklers
installed
not
more
than
3,2m
apart;
each
row
shall
be
the same
distance
from
the
nearest
shelf
edge.
The
sprinklers
at
a
particular
level
in
each
line
shall
be located
in
the
same
set
of
transverse
flues.
Where
any
rack
or
structural
steelwork
could
significantly
interfere
with
the
water
distribution
from
a sprinkler,
an
additional
sprinkler
shall
be
provided.
11.5.6 HHS intermediate sprinklers below solid or slatted shelves in racks (ST5 and ST6)
Intermediate
sprinklers
shall
provided
above
each
shelf
(including
the
top
shelf
if
the
roof
or
ceiling sprinklers
are
more
than
4m
above
the
goods
or
water
access
to
the
goods
is
restricted),
and
located
as
shown
in
Table
24
and
Figure
11.
The
vertical
distance
between
rows
shall
not
exceed
3,5m.
Single
rows
of
sprinklers
shall
be
central
above
shelves.
Double
rows
shall
be
positioned
so
that
each
row
is the
same
distance
from
the
nearest
shelf
edge.
The
distance
from
the
end
of
the
shelf
parallel
to
the
range
pipe
lines
to
the
nearest
sprinkler
shall
be
half
the sprinkler
spacing
along
the
range
lines
or
1,6m,
whichever
is
the
smaller.