86
12.2.2
to
12.2.4.
12.2.2 Ceiling or flush, recessed and concealed pattern
Ceiling
or
flush,
recessed
and
concealed
sprinklers
shall
not
be
installed
in
OH4,
HHP
or
HHS
areas.
Sprinklers
without
fixed
deflectors,
i.e.
with
retracted
deflectors
which
drop
to
the
operating
position
on actuation,
shall
not
be
fitted:
a)
where
the
ceiling
is
more
than
45°
from
the
horizontal;
b)
in
situations
where
the
atmosphere
is
corrosive
or
likely
to
have
a
high
dust
content;
c)
in
racks
or
under
shelves.
12.2.3 Sidewall pattern
Sidewall
sprinklers
shall
not
be
installed
in
HHP
or
HHS
installations
or
above
suspended
ceilings.
They
may
only
be
installed
under
flat
ceilings.
12.2.4 Flat spray pattern
The
use
of
flat
spray
sprinklers
shall
be
restricted
to
concealed
spaces,
suspended
open
ceilings
and
in
racks.
12.2.5 Extended coverage sprinkler
This
type
of
sprinkler
may
be
used
for
special
protection
e.g.
hotel
bedroom,
with
an
approval
by
the authorities.
Only
Quick
response
sensitivity
shall
be
used.
12.2.5.1
Extended
coverage
sidewall
sprinkler
Extended
coverage
sidewall
sprinklers
may
be
used
in
LH
and
OH1
hazards.
They
may
be
used
in
rooms, which
have
a
maximum
area
of
126
m²,
a
fire
resistance
of
the
compartment
of
at
least
30
minutes,
a
smooth ceiling
and
a
maximum
ceiling
height
of
4,1m.
In
one
area
only,
sprinklers
with
identical
response sensitivity
class
may
be
used.
The
area
per
sprinkler
must
not
exceed
21
m².
In
rooms
with
a
maximum
width
of
6,5
m,
only
one
row
of extended
coverage
sidewall
sprinklers
needs
to
be
installed
along
the
longitudinal
wall.
In
rooms
with
a width
of
between
6,5
m
and
11
m,
two
rows
of
extended
coverage
sidewall
sprinklers
must
be
installed
along each
of
the
longitudinal
walls.
In
this
case,
the
sprinklers
must
be
installed
staggered.
The
area
of
operation
with
extended
coverage
sidewall
sprinklers
shall
not
be
less
than
126
m².
The
minimum
design
pressure
shall
be
2,5
bar
for
ceiling
heights
up
to
2,8
m
and
3
bar
for
ceiling
heights between
2,8m
and
4,1m.
The
distance
between
two
extended
coverage
sidewall
sprinklers
installed
along
the
same
wall
shall
be between
3
m
and
4,5
m.
Extended
coverage
sidewall
sprinklers
shall
be
installed
at
a
maximum
distance
of
300
mm
from
the
adjacent
wall
and
at
a
distance
of
100
mm
to
250
mm
from
the
ceiling.
Extended
coverage sidewall
sprinklers
shall
be
installed
at
a
minimum
horizontal
distance
of
0,5
m
from