96
•
The
bending
strength
of
the
welded
pipe
joint
shall
be
at
least
80%
of
the
pipe
bending
strength;
•
If
robot
welding
machines
are
used,
the
welding
operation
shall
be
fully
automatic.
15.1.4 Mechanical pipe joints
Mechanical
pipe
joints
shall
be
approved.
15.1.5 Flexible pipes and joints
If
relative
movement
is
likely
to
occur
between
different
sections
of
pipework
within
the
sprinkler
system, e.g.
owing
to
expansion
joints
or
in
the
case
of
free-standing
storage
racking,
a
flexible
section
or
joint
shall
be
fitted
at
the
point
of
connection
to
the
distribution
main.
Before
installation
it
shall
meet
the
following requirements.
a)
it
shall
be
capable
of
withstanding
a
test
pressure
of
four
times
the
maximum
working
pressure
or
40 bar,
whichever
is
the
greater,
and
shall
not
include
parts
which,
when
subject
to
fire,
might
impair either
the
integrity
or
the
performance
of
the
sprinkler
system;
b)
Flexible
pipes
shall
contain
a
continuous
pressure-retaining
stainless
steel
or
non-ferrous
metal
inner tube;
c)
Flexible
pipes
shall
not
be
fitted
in
the
fully
extended
position.
Flexible
pipes
and
joints
shall
not
be
used
to
take
up
misalignment
between
a
distribution
main
and
the
feed pipes
to
intermediate
sprinklers.
15.1.6 Concealment
Pipes
shall
be
installed
in
such
a
way
that
they
are
easily
accessible
for
repairs
and
alterations.
They
shall
not
be
embedded
in
concrete
floors
or
ceilings.
NOTE:
wherever
possible,
piping
should
not
be
installed
in
concealed
spaces
which
make
inspection, repairs
and
modifications
difficult.
15.1.7 Protection against fire and mechanical damage
Piping
shall
be
installed
in
such
a
way
that
the
pipes
are
not
exposed
to
mechanical
damage.
Where
pipes
are installed
above
gangways
with
low
headroom,
or
at
intermediate
levels,
or
in
other
similar
situations,
precautions
shall
be
taken
against
mechanical
damage.
Where
it
is
unavoidable
for
water
supply
pipework
to
pass
through
an
unsprinklered
building,
it
shall
be installed
at
ground
level
and
shall
be
enclosed
by
dwarf
brick
walls
covered
by
concrete
slabs.
15.1.8 Painting
Non-galvanised
ferrous
pipework
shall
be
painted.
Galvanised
piping
shall
be
painted
wherever
the
coating has
been
damaged,
e.g.
by
threading.
NOTE:
extra
protection
may
be
needed
for
unusually
corrosive
conditions.
15.1.9 Drainage
Mean
shall
be
provided
to
enable
all
the
pipework
to
be
drained.
Where
this
cannot
be
done