CET Electric Technology
87
AI 0532
Interval kvarh Export*
R
AI 0534
Interval kVAh*
R
kWh
AI 1200
DI #1 Counter
R
-
0 to
999,999,999
AI 1202
DI #2 Counter
R
AI 1204
DI #3 Counter
R
AI 1206
DI #4 Counter
R
AI 1208
DI #5 Counter
R
AI 1210
DI #6 Counter
R
*There are no unit types for kvarh and kVAh in BACnet so the return values are in unit of kWh.
Notes:
1) When the Wiring Mode is 3P3W, the per phase line-to-neutral voltages, kWs, kvars, kVAs and
PFs have no meaning, and their registers are reserved.
2) Uan/Ubn/Ucn THD = Uab/Ubc/Uca THD in 3P3W Wiring Mode and represent the harmonics
of the line voltages.
3) Uan/Ubn/Ucn Angle = Uab/Ubc/Uca Angle in 3P3W Wiring Mode and represent the phase
angles of the line voltages.
4) Analog Value Objects (PMC-53A’s Basic Setup Registers)
Optional Properties Supported: Description, Relinquish_Default, Priority_Array
Writable Properties: Present_Value, Out_Of_Service, Units, Relinquish_Default
Use the Present Value property of the Analog Value object for some writable variables in the
meter other than those used specifically for BACnet configuration or Time Synchronization.
Values are checked when written, and errors are returned for invalid entries. The table below
describes how the Setup Registers of the PMC-53A are represented in BACnet, their valid ranges,
their defaults as well as how they are used. PMC-53A supports the Description,
Relinquish_Default and Priority_Array optional properties. Writable properties include
Present_Value, Out_Of_Service, Units and Relinquish_Default, but Units are not non-volatile
after modification.
Register
Description
Property
Unit/ Range
Default/Note
AV 6000
PT Primary High
#
R/W
0 to 1000 kV
0
AV 6001
PT Primary Low
#
R/W
1 to 999 V
100
AV 6002
PT Secondary
#
R/W
1 to 690
100
AV 6004
CT Primary
R/W
1 to 30000
5
AV 6006
CT Secondary
R/W
1 to 5
5
AV 6012
I4 Primary
R/W
1 to 30000
5
AV 6014
I4 Secondary
R/W
1 to 5
5
AV 6020
Wiring Mode
R/W
0 = DEMO
1 = 1P2W L-N
2 = 1P2W L-L,
3 = 1P3W L-L-N
4 = 3P3W, 5 = 3P4W
5
AV 6021
PF Convention
R/W
0 = IEC, 1 = IEEE, 2 = -IEEE
0
AV 6022
kVA Calculation
R/W
0 = Vector, 1 = Scalar
0
AV 6028
THD Calculation
R/W
0 = THDf, 1 = THDr
0
AV 6029
Demand Period
R/W
1 to 60 min
15
AV 6030
Number of Sliding Windows
R/W
1 to 15
1
AV 6047
Interval Energy Period
R/W
5 to 60 min
60
AV 9603
Clear Present Peak Demand
W
65280
Default = 0
Writing
“0xFF00” to the
register to
execute the
described
action.
AV 9601
Clear Energy
W
65280
AV 9610
Clear DI #1 Counter
W
65280
AV 9611
Clear DI #2 Counter
W
65280
AV 9612
Clear DI #3 Counter
W
65280
AV 9613
Clear DI #4 Counter
W
65280
AV 9614
Clear DI #5 Counter
W
65280

Table of Contents

Other manuals for CET PMC-53A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CET PMC-53A and is the answer not in the manual?

CET PMC-53A Specifications

General IconGeneral
BrandCET
ModelPMC-53A
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals