CF Control Operation and functions
6.3.12 Maximum daily dosing quantity
10
[parameters 15, 16]
It is possible to specify the max. daily dosing quantity separately for each dosing
output. The CF Control 100 adds up the dosing quantities which the respective pump
delivers. If the quantity is exceeded within a calendar day, a "Dosing time monitor"
alarm is triggered. Dosing is completely deactivated. The alarm must be reset using
the button.
If the parameter for the maximum daily dosing quantity is set to 0, a monitoring of the
appropriate dosing output is switched off.
6.3.13 Dosing capacity of pumps [parameters 88, 89]
If you establish that there are overshoots in the control of chlorine and pH
(overshooting of actual values), or that set points are not reached or not reached
within a reasonable time, you can try and use these settings to adapt the dosing
capacities of the pumps to your pool size.
6.3.14 Code for calibration [parameter 92]
You can prevent someone unauthorized from carrying out a pH calibration.
Go to the setting parameters as described above and select parameter 92; code B
must be set first:
Parameter
Function
Factory setting
92
Code for calibration:
0
If you select 0, the calibration can be carried out with any of the three codes; if you
select 1, the process is restricted to authorization codes B and C (specialist dealer -
dinotec service staff). A calibration with user code A is no longer possible in this
case.
10
This function is only recommended when using the water guard dosing 100 pumps!