EasyManua.ls Logo

ChemoformGroup CF Control 100 - Activation of the Heating; Changing from Heating Control to Solar Heating Control (Parameter 94); Reading the Temperature of the Solar Sensor [Parameter 8]

ChemoformGroup CF Control 100
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CF Control Settings
07/2017
Page
35
8.3 Activation of the heating
The heating circulation is connected by the CF Control 100 when the following
conditions are fulfilled:
1. The actual temperature of the pool water is below the adjusted set point
temperature for one minute.
2. The set switch-on delay has elapsed.
3. Sample water is circulating.
4. The filter pump is switched on.
When the water temperature has exceeded the set point for more then a minute, the
heating is deactivated.
8.4 Changing from heating control to solar heating control (parameter 94)
Press the Eingabe / ENTER button and choose parameter P 94.
When the value on the right is set to 0, only heating is activated.
/ ENTER
Set the value on the right to 1; as a result, the solar operation is activated:
/ ENTER
Press to return to the display level.
8.5 Reading the temperature of the solar sensor [parameter 8]
Press the Eingabe / ENTER button and choose parameter P 8.
The temperature is displayed in tenth of a degree.
12
The solar temperature sensor is not included.
WARNING: It is mandatory that a second solar temperature sensor is available for
the solar operation. It should always be positioned at the highest
place of the solar system.
12
NOTE: You can select either the heating operation or alternatively the solar
oper
ation.

Table of Contents