Troubleshooting
Troubleshooting Chore-Tronics® 3 Control
114
MT2398C
Programming Trouble Shooting
Problem Possible Cause Possible Solution
Can not lower set temperature
below 32.0° F. and can not raise
the set temperature above
120.0° F.
Normal set temperature range. The Control has been set up so
that
set temperature range is
between 40.0° F. and 120.0° F.
Have one Fan set to come on at
80°F an
d another Fan to come on
at 80.3°F, but the Control won’t
accept the 80.3° setting.
Offsets too close.
There must be at a .5°F difference
bet
ween any two Fan outputs.
Two or more Fans may be set to
come on at the same temperature.
Heater outputs follow the same
rules, however the cool out puts
do not.
Fan(s) turns on, Mode Sensor(s)
temperature is at se
t point.
A.) Fan is assigned to a Timer.
B.) Temperature Sensor(s)
assi
gned to operate the Fan
are different than the mode
Sensor(s).
C.) Fan’s manual switch is set to
th
e manual “on” position.
D.) Bad Relay Module/MS Board.
A.) If Timer is not wanted on Fan
r
emove the Timer in
the "Outputs and Tempera-
tures" screen.
B.) Change Temperature Sen-
sor(s) assignments in the
Setup-General: Ou
tputs
Screen if desired.
C.) Put manual switch in “auto-
matic” position.
D.) Replace Module/Board
Fan(s) will not turn on when mode
Sens
or(s) reach the Fan’s on tem-
perature.
A.) Fan’s assigned Sensor(s) are
dif
ferent than the mode Sen-
sor(s)
B.) Fan is set to run in a different
m
ode (example: Tunnel
instead of Power).
C.) Fan’s manual switch is set to
th
e “off” position.
D.) Bad Relay Module/MS Board.
A.) Change Temperature Sen-
sor(s) assignments if desired.
B.) Go to the "Setup" screen and
change modes
of operation if
desired.
C.) Put manual switch in “auto-
matic” position.
D.) Replace Module/Board
Fan(s) will not shut off. A) Fan has not reached the “off”
te
mperature.
B.)Fan assigned Temperature Sen-
sor(s) is different than mode
T
emperature Sensor(s).
C.) Fan’s manual switch is set to
th
e manual “on” position.
D.) Bad Relay Module.
E.) Back-up thermostat is overrid-
ing the Control.
A.) The Fan’s “off” temperature is
the “on” tempe
rature of the
next Fan below it, or if
desired you can program the
"off" temperature.
B.) Change Temperature Sen-
sor(s) assignments in the
Setup-General: Ou
tputs
screen if desired.
C.) Put manual switch in “auto-
matic” position.
D.) Replace Module/Board.
E.)Check setting of back-up ther-
mostat and correct if neces-
sary.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Chore-Time Chore-Tronics 3 Control and is the answer not in the manual?

Chore-Time Chore-Tronics 3 Control Specifications

General IconGeneral
BrandChore-Time
ModelChore-Tronics 3 Control
CategoryHome Automation
LanguageEnglish