Control Setup Chore-TronicsĀ® 3 Control
42
MT2398C
Ventilation-Cool
The Cool outputs can be used for cool pads, fogger pads and or inside foggers. The Cool output can be
setup to be on/off based the temperature setting in the Output & Temperature. A t
imer can be assigned to
the Cool output. If a timer is assigned, at the on temperature the output will start timing on/off based on
the timer setting and will not run constant.
Sixteen Cool outputs can be assigned up to four relays per Cool output.
1. Select the Ventilation button.
2. Select the Cool button to assign the Cool outputs..
3. Assign Relays, Sensors and Mode
values to each Cool item.
Relays
Mode
Sensors