EasyManua.ls Logo

Chore-Time Chore-Tronics 3 Control - Page 60

Chore-Time Chore-Tronics 3 Control
142 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Control Setup Chore-TronicsĀ® 3 Control
60
MT2398C
Cool Setting
1. Select the Main menu button. Select the Ventilation Settings button.
2. Select the Cool button.
3. Cool Outputs Disabled Above RH- If there are
relays assigned to cool output(s), and a relative hu-
midity sensor is connected to the Control, the Con-
trol can block the cool output from turning on if the
relative humidity sensor reading is higher than en-
tered value.
4. Allow Cool From- User can also specify a specific time of day in which the cool outputs
are allowed to operate. A setting of 12:00a to 12:00a means that the cool outputs are allowed
to operated 24 hours per day.
5. Do Not Allow Cool To Go Below- Outputs
can have a minimum temperature setting. If the
cool or Cool Pad outputs reach this minimum
temperature due to the set temperature changing
the outputs will not go below this minimum tem-
perature even though the set temperature may
continue to lower due to the set temperature
curve.
34
5

Table of Contents