EasyManuals Logo

Chore-Time Chore-Tronics 3 Control User Manual

Chore-Time Chore-Tronics 3 Control
142 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #97 background imageLoading...
Page #97 background image
Control Installation Chore-Tronics® 3 Control
97
MT2398C
Temperature Sensors Continued.....
Route the wire through the back of the Temperature Sensor and connect it as shown in Figure below. Pull the
wire through the back of the box until a drip loop is formed as shown.
Mv1701-010 10/01
3
1
Front View
(with Lid Off)
2
Figure 21. Drip Loop
Item Description
1 Temperature Sensor (Back Side)
2 Non-Shielded Twisted Pair
3 Drip Loop
Static Pressure (SP) Wiring
There is a Static Pressure Sensor included with every Chore-Tronics
®
3 Control. This sensor is pre-wired
from the factory to Analog Input #4 (AI 4) (Figure 22). If it is desired, the Static Pressure Sensor can be
wired to any of the Analog Inputs (AI1 through AI16) (See Figure 23 for example wired to AI1). Please
note that the Red wire must always be connected to the +24 volt terminal, the Blue wire must be connected
to the AI terminal being used and the Black wire must be connected to the ground terminal of the analog
Input being use. Make sure that whichever AI Input the SP sensor is connected to, that the blue jumper
above the Input is set to "U" position as shown.
AI15
24V
A6I1
AI1
24V
AI2
U
R
I
Figure 23. Static Pressure Sensor
Wired to AI1
Blue Jumper in the "U" position
Blue Jumper in the "U" position
Figure 22. Static Pressure Sensor
Pre-wired to AI15
Black
Red
Red
Black

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Chore-Time Chore-Tronics 3 Control and is the answer not in the manual?

Chore-Time Chore-Tronics 3 Control Specifications

General IconGeneral
BrandChore-Time
ModelChore-Tronics 3 Control
CategoryHome Automation
LanguageEnglish