Programmable DC Electronic Load 63600 Series Operation & Programming Manual
5-70
5.3.2.12 POWER Subsystem
:
STATic
:FALL
:L2
:L1
SP
<NRf+>
?
SP
MAX
MIN
SP
<NRf+>
?
SP
MAX
MIN
<NR2>
Suffix
<NR2>
<NR2>
<NR2>
<NR2>
<NR2>
:POWer
:RISE
Suffix
POWer:STATic:FALL
Type: Channel-Specific
Description: Set the falling slew rate of current for constant power mode.
Setting Syntax: POWer:STATic:FALL<space><NRf+>[suffix]
Setting Parameters:Refer to respective specification for valid value range.
Setting Example: POW:STAT:FALL 2.5 Set falling slew rate to 2.5A/μs.
POW:STAT:FALL 1A/μs Set falling slew rate to 1A/μs.
POW:STAT:FALL MAX Set falling slew rate to the
maximum value.
POW:STAT:FALL MIN Set falling slew rate to the
minimum value.
Query Syntax: POWer:STATic:FALL?[<space><MAX | MIN>]
Return Parameters:<NR2>, [Unit = A/μs]
Query Example: POW:STAT:FALL?
POW:STAT:FALL? MAX
POW:STAT:FALL? MIN
POWer:STATic:L1
Type: Channel-Specific
Description: Set the static load power for constant power mode.
Setting Syntax: POWer:STATic:L1<space><NRf+>[suffix]
Setting Parameters:Refer to respective specification for valid value range.
Setting Example: POW:STAT:L1 20 Set the load parameter L1 = 20W.
POW:STAT:L1 10W Set the load parameter L1 = 10W.
POW:STAT:L1 MAX Set the load parameter L1 = maximum
value.
POW:STAT:L1 MIN Set the load parameter L1 = minimum
value.
Query Syntax: CURRent:STATic:L1?[<space><MAX | MIN>]
Return Parameters:<NR2>, [Unit = Watt]
Query Example: CURR:STAT:L1?
CURR:STAT:L1? MAX
CURR:STAT:L1? MIN
POWer:STATic:L2
Type: Channel-Specific
Description: Set the static load power for constant power mode.
Setting Syntax: POWer:STATic:L2<space><NRf+>[suffix]