7.3.8.5.- Type of installation
Table 79: Modbus memory map: Type of installation
Type of installation
Configuration variable Address Valid data margin
Default
value
Type of installation 2B5C
0: 4-3PhThree-phase network with 4 wires.
1: 3-3PhThree-phase network with 3 wires.
2: 3-ArOnThree-phase network with 3 wires, Aron.
3:3-2Ph Two-phase network with 3 wires.
4: 2-2Ph Single-phase network with 2 wires, phase-to-phase.
5: 2-1Ph Single-phase network with 2 wires, phase-to-neutral.
0
7.3.8.6.- Maximum demand
Table 80: Modbus memory map: Maximum demand
Maximum demand
Configuration variable Address Valid data margin
Default
value
Integration period 274C 0
(5)
- 60 minutes 15
Type of integration 274D
0: Sliding window
1: Fixed window
0
(5)
Programming the value 0 disables the calculation of the maximum demand.
Note: When modifying the maximum demand configuration variables, the device restarts the calculation
of the maximum demand.
7.3.8.7.- THD calculation
Table 81:Modbus memory map: THD calculation.
THD calculation
Configuration variable Address Valid data margin
Default
value
THD calculation 2774
0: thd, Calculation using the effective value (RMS).
1: THD, Calculation using the fundamental value.
0
7.3.8.8.- Operating profile
Table 82: Modbus memory map: Operating profile
Operating profile
Configuration variable Address Valid data margin
Default
value
Operating profile 2B60
0: Analyzer
1: User
2: Electrical energy efficiency, e
3
0
7.3.8.9.- Display backlight
Table 83: Modbus memory map: Backlight
Backlight
Configuration variable Address Valid data margin
Default
value
Backlight 2B5E
0: Always lit
0 - 99 seconds
0