7.3.8.10.- Activating the harmonics display screen
Table 84: Modbus memory map: Display of harmonics
Display of harmonics
Configuration variable Address Valid data margin
Default
value
Display of harmonics 2B62
0: No
1: Yes
1
7.3.8.11. - CO
2
consumption and generation emissions.
Table 85: Modbus memory map: CO
2
consumption and generation emissions.
CO
2
emissions
Configuration variable
(6)(7)
Address Valid data margin
Default
value
Tariff 1 consumption emissions ratio 2724 0 - 1.9999 0
Tariff 2 consumption emissions ratio 2725 0 - 1.9999 0
Tariff 3 consumption emissions ratio 2726 0 - 1.9999 0
Tariff 1 generation emissions ratio 2728 0 - 1.9999 0
Tariff 2 generation emissions ratio 2729 0 - 1.9999 0
Tariff 3 generation emissions ratio 272A 0 - 1.9999 0
(6)
All variables must be programmed at the same time.
(7)
They have 4 decimal place.
7.3.8.12.- Cost of energy consumption and generation.
Table 86: Modbus memory map: Cost of energy consumption and generation.
Cost per kWh
Configuration variable
(8)(9)
Address Valid data margin
Default
value
Cost per kWh of tariff 1 consumption 272C 0 - 1.9999 0
Cost per kWh of tariff 2 consumption 272D 0 - 1.9999 0
Cost per kWh of tariff 3 consumption 272E 0 - 1.9999 0
Cost per kWh of tariff 1 generation 2730 0 - 1.9999 0
Cost per kWh of tariff 2 generation 2731 0 - 1.9999 0
Cost per kWh of tariff 3 generation 2732 0 - 1.9999 0
(8)
All variables must be programmed at the same time.
(9)
They have 4 decimal place.
7.3.8.13.- Programming alarms 1 and 2 (Relays 1 and 2)
Table 87: Modbus memory map: Programming alarms 1 and 2.
Programming alarms 1 and 2
Configuration variable
Address
Valid data margin
Default
value
Relay 1 Relay 2
Maximum value 2AF8-2AF9 2B02-2B03 depending on the variable 0
Minimum value 2AFA-2AFB 2B04-2B05 depending on the variable 0
Variable code 2AFC 2B06 Table 43 and Table 44 0
Connection delay 2AFD 2B07 0 - 9999 seconds 0
Hysteresis 2AFE 2B08 0 - 99 % 0