Digital inputs
Quantity 2
Type NPN
Insulation 2000 V
Max. current in short circuit 4 mA
Max. voltage in open circuit 17 V
Digital outputs
Quantity 2
Type NPN
Maximum voltage 24 V
Maximum current 50 mA
Maximum frequency 16 impulses / sec
Pulse width 300 ms to 400 ms
Communications
Modbus RTU BACnet
Bus RS-485 MS/TP
Protocol Modbus RTU BACnet
Baud rate 9600 - 19200 - 38400 bps
Stop bits 1 - 2 1
Parity without - even - odd without
User interface
Display LCD Custom COG
Keyboard 3 keys
LED 2 LED
Environmental features
Operating temperature -25ºC ... +70ºC
Storage temperature -25ºC ... +75ºC
Relative humidity (non-condensing) 5 ... 95%
Maximum altitude 2000 m
Protection degree IP
IP20, Front panel: IP54
Protection degree IK
IK08
Pollution degree
2
Use
Indoor
Mechanical features
Terminals
1, 2, 14 ... 17, 9 ... 13, 18 ... 25 0.2 ... 2.5 mm
2
0.5 ... 0.6 Nm
M3
3 ... 8 0.2 ... 1.5 mm
2
0.2 ... 0.25 Nm
M2
Dimensions ( Figure 24) 96 x 96 x 67.2 mm
Weight 353 g.
Surround Self-extinguishing V0 plastic
Attachment Panel
91
Instruction Manual
CVM-C11