Chapter 5 Removal and Replacement Procedures
Removing and Replacing the Power Supply
Figure 5-100 DC-Input Wire Connections for 6000-W DC-Input Power Supply for Left Side of Power
Bay
b. From the left side of the power supply, connect each of the DC-input wires to the terminal block
(
Figure 5-97 and Figure 5-100) in this order:
Negative (-)
Positive (+)
Note When you tighten the terminal nuts, make sure they are snug. Do not over tighten them.
Recommended torque strength is 20 inch-pounds. Over tightening the terminal nuts can
break the terminal block (Maximum torque: 36 inch-pounds).
Step 9 Wire for 2800 W (right side of power supply bay) as follows:
a. From the right side of the power supply, connect the ground wire to the ground (Figure 5-101).