Section 2 — Installation
Part No. 750-263 2-7
18.Remove control panel from box. Uncoil sensor wires and route wires out
of left-hand side of panel.
19.Mount control panel on front of boiler (Figure 2-11). Make sure to route
sensor wires in wiring channel on left-hand side of the boiler (see also
Figure 2-41).
20.Connect control wiring (Figure 2-12):
Connect flame rod cable (A) to stand alone electrode on right
(includes burner ground connection).
Connect ignition cables (B) to dual igniter electrode.
Connect remaining connectors per connection diagram (see
Figure 2-41).
Figure 2-10
Figure 2-11