15.2.1.21  Binary output: Common Wrn 
The output is closed while there is at least one alarm of the Warning type 
present in the alarm list. The alarm can be in any state, i.e. active 
unconfirmed, active confirmed or inactive unconfirmed. See the chapter 
Alarm management for more information. 
 
15.2.1.22  Binary output: Common Fls 
The output is closed while there is at least one alarm of the Sensor fail type 
present in the alarm list. The alarm can be in any state, i.e. active 
unconfirmed, active confirmed or inactive unconfirmed.See the chapter Alarm 
management for more information. 
 
15.2.1.23  Binary output: Common BOp 
This output closes if any "Breaker Open" type alarm appears. The output 
opens if no BO type alarm is active (pressing of fault reset button is not 
required). 
 
15.2.1.24  Binary output: Common BOR 
This output closes if any "Breaker Open with fault reset" type alarm appears. 
The output opens if no BOR type alarm is active (pressing of fault reset 
button is required). 
 
15.2.1.25  Binary output: Common Al 
The output is closed while there is at least one alarm of the Alarm only type 
present in the alarm list. The alarm can be in any state, i.e. active 
unconfirmed, active confirmed or inactive unconfirmed. See the chapter 
Alarm management for more information.