15.2.1.64  Binary output: PeriphCommErr 
The output is closed while there is an error in the communication with any 
peripheral unit (e.g. IS-AIN8, IGS-PTM, ...). 
 
15.2.1.65  Binary output: WrongPhSeq 
Binary output WrongPhSeq is active when at least one of the following 
conditions is fulfilled: BusL/BusR phase is inverted or wrong BusL/BusR 
phase sequence or opposed BusL/BusR phase sequence is detected.  
 
15.2.1.66  Binary output: User Button 1 
This output can be specified for example on buttons on IV-5/8 or in SCADA 
diagram in InteliMonitor. Its state depends on function assigned to the related 
button.  
It is possible to lock UserButton commands in configuration to specific user 
level. Buttons 1-8 and 9-16 are locked separately.  
 
Pressing the button changes the state of log. binary output 
User Button X to closed. When the output is closed and the 
button is pressed state is not changed.  
Pressing the button changes the state of log. binary output 
User Button X to opened. When the output is opened and 
the button is pressed state is not changed.  
Pressing the button changes the state of log. binary output 
User Button X to opened or closed depending on previous 
state (it is changed to the opposite state).  
Pressing the button issues log. binary output User Button X 
to close for one second.  
NOTE:  
Repeated pressing of button during the closed period (one 
second) causes issuing another puls of length of one 
second to be generated from the moment of button 
pushing.