InteliATS
NT
PWR, SW version 2.5, ©ComAp – May 2015 44
IA-NT- PWR-2.5-Reference Guide.pdf
Inputs and Outputs
For Inputs/Outputs overview table see chapter Technical Data.
NOTE:
Any Binary input or output can be configured to any IA-NT controller terminal or changed to different
function by LiteEdit software. There is fix 1 sec delay when any binary input is configured as
protection.
Not Used
Binary input has no function. Use this configuration when Binary input is not connected.
Alarm
If the input is closed (or opened) selected alarm is activated.
Binary Alarm configuration items