Table of Diagnostic Codes:
Code
Description
0
OK. No error.
1
Not possible to hang up.
2
IL-NT-GPRS is switched off
3
IL-NT-GPRS is switched on
4
IL-NT-GPRS error in initialization
5
IL-NT-GPRS not possible to set the APN
6
IL-NT-GPRS not possible to connect to GPRS network
7
IL-NT-GPRS not possible to retrieve IP address
8
IL-NT-GPRS not accepted DNS IP address
9
Error in modem detection
10
Error in initialization of analog modem
11
SIM card is locked (Possibly PIN code required, PIN needs to be deactivated) or unknown
status of SIM locking
12
No GSM signal
13
Not possible to read the SIM card parameters
14
GSM modem did not accepted particular initialization command, possibly caused by
locked SIM card
15
Unknown modem
16
Bad answer to complement initialization string
17
Not possible to read GSM signal strength
18
CDMA modem not detected
19
No CDMA network
20
Unsuccessful registration to CDMA network
23
Controller couldn´t detect IL-NT GPRS module communication speed.
255
Only running communication is needed to indicate
AirGate Diag Diagnostic Code for AirGate connection
Table of Diagnostic Codes:
Code
Description
0
Waiting for connection to AirGate Server
1
Controller registered, waiting for authorization
2
Not possible to register, controller blacklisted
3
Not possible to register, server has no more capacity
4
Not possible to register, other reason
5
Controller registered and authorized
AirGate
technology for easy plug-and-play wireless communication is incorporated into the product. An
ordinary SIM card with GPRS service is suitable for this system. This overcomes problems with the
necessity for a special SIM card (fixed and public IP), firewalls and difficult communication settings.
http://www.comap.cz/news-room/news-and-events/detail/AirGate
http://www.comap.cz/news-room/news-and-events/detail/The-Rainbow-rises-for-remotemonitoring-
applications/
Locate
The controller supports the technology for GSM localization using an IL-NT-GPRS
communication module. It is possible to view the localization in WebSupervisor.