InteliATS
NT
PWR, SW version 2.5, ©ComAp May 2015 64
IA-NT- PWR-2.5-Reference Guide.pdf
DNS IP Address [-]
If DHCP is DISABLED this setpoint is used to adjust the domain name server (DNS), which is needed
to translate domain names in e-mail addresses and server names into correct IP addresses.
If DHCP is ENABLED this setpoint is used to display DNS server, which has been assigned by the
DHCP server.
Engine Params
Prestart Time [s]
Time of closing of the Prestart and/or Pretransfer output prior to the engine start.
Set to zero if you want to leave the output Prestart/Pretransfer open.
Step: 1 s
Range: 0 600 s
Cooling Time [s]
Runtime of the unloaded gen-set to cool the engine before stop.
Step: 1 s
Range: 0 3600 s
Max Start Del [s]
This timeout starts after closing binary output GEN START/STOP. When generator does not reach
defined limits Basic Settings: Nominal Freq) within Max Start Del, Trp Start Fail alarm occurs and the
gen-set will shut down. See the table below for a description of the engine start evaluation.
If Max Start Del is longer than 600 s it means there is NO TIMEOUT.
Step: 1 s
Range: 0 600 s, 601 s = NO TIMEOUT