InteliATS
NT
PWR, SW version 2.5, ©ComAp – May 2015 75
IA-NT- PWR-2.5-Reference Guide.pdf
Timer1..2Duration
Duration of Timer output is active.
Step: 1 min
Range: 1 – 1440 s
SMS/E-Mail
Remote alarm messaging
If a GSM modem and/or InternetBridge-NT is connected to the controller, the controller can send SMS
messages and/or emails in the moment when a new alarm appears in the Alarm list. The message will
contain a copy of the Alarm list.
To enable this function, you should select with setpoints Yel Alarm Msg and Red Alarm Msg, which
levels of alarms shall be announced (red/yellow/both) and also enter valid GSM phone number and/or
e-mail address to the setpoints TelNo/Addr Ch1 and TelNo/Addr Ch2. It is possible to put either a
GSM number or e-mail to both setpoints.
The list of all supported terminals shows the table below:
*since IB-NT 2.2.0
Controller is capable to detect which communication terminal is connected to the network and send
the email/SMS via the active one. InternetBridge-NT is preferred terminal if more possibilities are
detected.
NOTE:
An internet module must be available for sending of e-mails. Similarly, a GSM modem is necessary for
sending of SMS.
NOTE:
There are 5 attempts for any active call (SMS/E-Mail). Timeout for connection is 90 sec and after 120
sec controller starts the next attempt. During the time the IA-NT is trying to send an active call type,
incoming calls are blocked.
Yel Alarm Msg [DISABLED, ENABLED]
Set this setpoint to YES if you want to get messages when a yellow (warning) alarm occurs.
NOTE:
The target address (GSM phone number or e-mail address) must be set correctly to the setpoint(s)
TelNo/Addr Ch1 resp. TelNo/Addr Ch2.
Red Alarm Msg [DISABLED, ENABLED]
Set this setpoint to YES if you want to get messages when a red (Trip) alarm occurs.
NOTE:
The target address (GSM phone number or e-mail address) must be set correctly to the setpoint(s)
TelNo/Addr Ch1 resp. TelNo/Addr Ch2.
TelNo/Addr Ch1, 2
Enter either a valid GSM phone number or e-mail address to this setpoint, where the alarm messages
shall be sent. Type of active call is considered from the value of this parameter. If it consist „@“ it is