InteliATS
NT
PWR, SW version 2.5, ©ComAp May 2015 74
IA-NT- PWR-2.5-Reference Guide.pdf
Date/Time
Time Stamp Per [min]
Time interval for periodic history records. Adjust the setpoint to 0 to disable this function.
Step: 1 min
Range: 0 200min
NOTE:
Time stamps are only recorded into history while gen-set is running. When is engine stopped there are
no time stamps records made.
SummerTimeMod [DISABLED / WINTER / SUMMER, WINTER-
S, SUMMER-S]
DISABLED: Automatic switching between summer and wintertime is disabled.
WINTER (SUMMER): Automatic switching between summer and wintertime is enabled and it is set to
winter (summer) season.
WINTER-S (SUMMER-S): Modification for southern hemisphere.
Time [HHMMSS]
Real time clock adjustment.
Date [DDMMYYYY]
Actual date adjustment.
Timer1..2Function [No Func / TEST / TEST OnLd / MFail Blk /
Mode OFF / Rem Trans]
It is possible to choose out of 6 following Timer functions. Binary output Exerc Timer X is always
activated when Timer is active regardless of chosen Timer function. Timer functions require controller
running in AUT mode.
No Func: There is no any other function, but binary output Timer1..2 activation.
TEST: When this option is chosen then the Timer output is also internally connected to the
Remote TEST binary input.
TEST OnLd: When this option is chosen then the Timer output is also internally connected to the
Rem TEST OnLd binary input.
MFail Blk: When this option is chosen then the Timer output is also internally connected to the
MainsFailBlock binary input.
Mode OFF: When this option is chosen then the Timer output is also internally connected to the
Remote OFF binary input.
Rem Trans: When this option is chosen then the Timer output is also internally connected to the
Remote Transfer binary input.
Timer 1..2 Repeat
[NONE/MONDAY/TUESDAY/WEDNESDAY/THURSDAY/WEDNESDAY/FRI
DAY/SATURDAY/SUNDAY/MON-FRI/MON-SAT/MON-SUN/SAT-SUN]
Defines TIMER 1 activation. Binary output TIMER 1 is internally linked with Rem Start/Stop binary
input. Refer to binary inputs for details.
NONE: Timer function is disabled
MONDAY, TUESDAY, WEDNESDAY, THURSDAY, WEDNESDAY, FRIDAY, SATURDAY, SUNDAY:
Timer is activated on daily basis.
MON-FRI, MON-SAT, SAT-SUN:
Timer is activated on selected day interval.
Timer1..2 ON Time
Day time when Timer output activates.