Circuit breakers timing
Relation between Mains fail and MCB and start of gen-set
MCB Opens On = MAINSFAIL:
Mains fail is detected as Mains <V, Mains >V, Mains V Unbal, Mains <Freq, Mains >Freq. After
detection MCB is opened.
NOTE:
When MCB feedback drop-out and measured mains electrical limits (voltage, frequency) are still in
limits, the controller switches MCB ON again.
Relation between Mains return and MCB
OFF Mode, GCB and MCB are opened