EasyManuals Logo

ComAp InteliLite 4 AMF 20 User Manual

ComAp InteliLite 4 AMF 20
620 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #255 background imageLoading...
Page #255 background image
InteliLite4 AMF20 Global Guide
255
Subgroup: Ventilation
Ventilation Pulse Time
Setpoint group Engine settings Related FW 1.3.0
Range [units] 0–3600 [s]
Default value 30 s Alternative config NO
Step 1 s
Comm object 15767 Related applications AMF,MRS
Config level Advanced
Setpoint visibility
Only when logical binary output VENTILATION ON PULSE (PAGE 504) or VENTILATION
OFF PULSE (PAGE 504) is configured.
Description
This setpoint defines duration of pulse generated on logical binary outputs VENTILATION ON PULSE (PAGE
504) or VENTILATION OFF PULSE (PAGE 504) at the moment when logical binary output VENTILATION (PAGE
504) is activated or deactivated respectively.
6 back to List of setpoints
Subgroup: ECU Settings
ECU Speed Adjustment
Setpoint group Engine settings Related FW 1.3.0
Range [units] 0 .. 100 [%]
Default value 50 % Alternative config NO
Step 1 %
Comm object 9948 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Visible only if ECU is configured
Description
Enables to adjust engine speed in ECU via CAN bus. Nominal speed corresponds to 50%. This setpoint
should be used only for Volvo Penta and Scania engines. It has no effect on other engine brands.
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 4 AMF 20 and is the answer not in the manual?

ComAp InteliLite 4 AMF 20 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 4 AMF 20
CategoryController
LanguageEnglish

Related product manuals