InteliLite4 AMF20 Global Guide
254
Subgroup: Pulse Counters
Conversion Coefficient Pulse 1
Setpoint group Engine settings Related FW 1.3.0
Range [units] 0 ... 1 000 [-]
Default value 1 Alternative config NO
Step 1
Comm object 10994 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Only if LBI PULSE COUNTER 1 (PAGE 455) is configured
Description
This setpoint adjusts the rate of increasing of the Pulse Counter 1 function. The module counts pulses at
the input PULSE COUNTER 1 (PAGE 455) and if the input pulses counter reaches value given by this
setpoint, the counter value Pulse Counter 1 (page 415) is increased by 1 and input pulses counter is
reset to 0. Both counter value and input pulses counter are stored in the nonvolatile memory.
6 back to List of setpoints
Conversion Coefficient Pulse 2
Setpoint group Engine settings Related FW 1.3.0
Range [units] 0 ... 1 000 [-]
Default value 1 Alternative config NO
Step 1
Comm object 10995 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Only if LBI PULSE COUNTER 2 (PAGE 456) is configured
Description
This setpoint adjusts the rate of increasing of the Pulse Counter 2 function. The module counts pulses at
the input PULSE COUNTER 2 (PAGE 456) and if the input pulses counter reaches value given by this
setpoint, the counter value Pulse Counter 2 (page 415) is increased by 1 and input pulses counter is
reset to 0. Both counter value and input pulses counter are stored in the nonvolatile memory.
6 back to List of setpoints