InteliLite4 AMF20 Global Guide
269
Group: Mains Settings
Subgroup: AMF Timers
Emergency Start Delay
Setpoint group Mains Settings Related FW 1.3.0
Range [units] 0 .. 6 000 [s]
Default value 5 s Alternative config NO
Step 1 s
Comm object 8301 Related applications AMF
Config level Standard
Setpoint visibility Conditioned by the setpoint Default Application Select (page 217)
Description
Delay after the mains failure to the start command of the Gen-set.
Image 8.16 Emergency Start Delay
6 back to List of setpoints
Mains Return Delay
Setpoint group Mains Settings Related FW 1.3.0
Range [units] 1 .. 3 600 [s]
Default value 20 s Alternative config NO
Step 1 s
Comm object 8302 Related applications AMF
Config level Standard
Setpoint visibility Conditioned by the setpoint Default Application Select (page 217)
Description
This setpoint adjust the delay, how long mains has to be returned after mains fail to start load transfer to
mains.
6 back to List of setpoints