InteliLite4 AMF20 Global Guide
328
Subgroup:Fence 2
Fence 2 Protection
Setpoint group Geo-Fencing Related FW 1.3.0
Range [units] HistRecOnl / Wrn / Sd / BOC[-]
Default value HistRecOnl Alternative config NO
Step [-]
Comm object 14611 Related applications AMF,MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Protection type for geo-fencing 2 protection. Fence of circle area is adjusted by setpoint Fence 2 Radius
(page 329). Delay for protection is adjusted by setpoint Fence 2 Delay (page 329).
HistRecOnl Position of gen-set is only measured and displayed on the LCD screen but not used
for protection. History record is made if position is out of Fence 2 Radius (page
329).
Wrn Position of Gen-set is used for warning protection only. Protection is activated when
position of the Gen-set is out of Fence 2 Radius (page 329).
Sd Position of Gen-set is used for shutdown protection. Protection is activated when
position of the Gen-set is out of Fence 2 Radius (page 329).
BOC Position of Gen-set is used for BOC (Breaker Open and Cooling) protection.
Protection is activated when position of the Gen-set is out of Fence 2 Radius
(page 329).
Protection types
Note: Protection is activated also when GPS signal is lost for Fence 2 Delay (page 329).
6 back to List of setpoints